The FLIR A70 and A40 thermal imaging cameras become the first thermal imaging detectors listed to UL 2684 to meet NFPA 72:2025.
Early fire detection is a major challenge for industries that handle large amounts of energy, combustible materials, or critical equipment. In applications such as battery storage, data centers, warehouses, electrical facilities, and industrial processes, detecting a thermal anomaly before smoke or flames appear can make a significant difference in the response to a potential fire.
Infrared thermography has been used for years to identify hot spots and abnormal conditions in equipment and facilities. However, there was a significant difference between using a thermal imaging camera as a monitoring tool and formally using it as part of a fire detection and alarm system.

What is UL 2684?
The ANSI/CAN/UL 2684 standard, Video and Thermal Image Detectors for Fire Alarm Systems, establishes requirements for devices that use video images and/or thermal images for fire detection.
This is particularly relevant because, while a conventional industrial thermal imaging camera may be capable of measuring temperature, triggering alarms, and detecting hot spots, those capabilities alone do not mean the equipment has been evaluated as a fire detector. UL 2684 listing provides a specific evaluation of the device for this function.
What is the relationship between UL 2684 and NFPA 72:2025?
The 2025 edition of NFPA 72, National Fire Alarm and Signaling Code, incorporates a specific section for thermal imaging detection systems: Section 17.12, Thermal Image Fire Detection.
One of the fundamental points of this section establishes that thermal imaging fire detection systems and their components must be “listed for the purpose of fire detection.”
Therefore, NFPA 72:2025 should not be interpreted simply as a requirement for a camera to bear a specific brand or certification. The fundamental requirement is that the equipment used as a detector be listed for that function which is precisely the classification provided by UL 2684.

How does the A70 integrate with an alarm system?
One of the key advantages of the A70 architecture is that detection does not necessarily rely on an external server to determine the existence of an alarm condition.
One of the key advantages of the A70 architecture is that detection does not necessarily rely on an external server to determine the existence of an alarm condition.
The A70 features outputs for:
Alarmr: Indicates that a thermal condition configured as an alarm has been reached.
Supervisory: Allows for the reporting of a condition that may affect detection capability, such as a condition related to the obstruction or contamination of the optics.
Fault: Allows signaling a device fault condition.
These signals can be integrated with control systems and fire alarm panels using the corresponding integration architecture.
In addition, the A70 incorporates communication protocols such as Modbus TCP, MQTT, EtherNet/IP, and ONVIF, enabling simultaneous integration with industrial platforms, SCADA, BMS, or VMS systems when the project requires it.

Detection prior to smoke or flame
One of the main advantages of thermal detection is that it allows for the direct observation of the asset’s temperature behavior.
In a typical incident development sequence, a component may begin to heat up abnormally before producing smoke or a visible flame.
A fixed thermal camera can identify that progression and generate an alert at an early stage.
This can be particularly relevant in applications such as:
- Battery Energy Storage Systems (BESS)
- Battery and UPS rooms
- Data centers
- Warehouses and logistics centers
- Photovoltaic installations
- Electrical substations
- Industrial plants
- Combustible material storage areas
- Industrial processes with a risk of auto-ignition
A major shift for fire protection engineering
The inclusion of thermal imaging detection in NFPA 72:2025 represents a significant change for fire protection system designers.
Until now, thermography had been widely used as a tool for predictive maintenance and prevention; however, the specific incorporation of this technology into the code provides a more defined framework for its use as part of fire detection systems.
The UL 2684 listing for the FLIR A70 also provides an independent reference demonstrating that the device has been specifically evaluated for this function.

Of course, having an A70 listed under UL 2684 does not mean that any installation using an A70 is automatically compliant with NFPA 72. NFPA 72:2025 establishes specific requirements for the use of thermal imaging detection systems, including aspects related to:
- Detector location and spacing
- Line of sight to the protected area or asset
- System configuration
- Detector operation monitoring
- Software and configuration changes
- System testing
- Integration with the alarm system
Therefore, a professional solution must consider not only which camera to use but also where to install it, the area it can monitor, the thermal resolution achieved on the target, the conditions that should trigger an alarm, and how that alarm will integrate with the fire protection infrastructure.
At bcb , we view thermography as a technology that must be integrated into the process, rather than simply as a camera installed in front of the equipment.